Copper Conductor XLPE Insulated Power Cable

关闭
产品咨询
客服热线:400-700-9997


Technical Parameters:

No.of cores x Nominal section areaNominal Construction of conductorNominal
Insulation
thickness
Nominal
Sheath thickness
Nominal
Overall diameter
Nominal
Cable weight
Max.Resistance of conductor
at 20ºC
No.X mm²No.X mmmmmmmmkg/km<=(Ω/km)
Three core   PVC Power Cables   CU/XLPE/PVC(  AL/XLPE/PVC ) 
3x1.52x 1.380,71,811.313012,10
3x2.57 x 0,670,71,811.81707,41
3x4.07 x 0,850,71,813.12304,61
3x6.07 x 1,040,71,813.93053,08
3x107 x 1,350,71,817.54501,83
3x167 x 1,700,71,818.26151,150
3x257 x 2,140,91,819.18700,727
3x357 x 2,520,91,821.111550,524
3x5019 x 1,781,01,823.815300,387
No.of cores x Nominal section areaNominal Construction of conductorNominal
Insulation
thickness
Nominal
Sheath thickness
Nominal
Overall diameter
Nominal
Cable weight
Max.Resistance of conductor
at 20ºC
No.X mm²No.X mmmmmmmmkg/km<=(Ω/km)
Four core  PVC Power Cables   CU/XLPE/PVC(  AL/XLPE/PVC )
4x1.52x 1.380,71,812.115012,10
4x2.57 x 0,670,71,813.22007,41
4x4.07 x 0,850,71,814.92754,61
4x6.07 x 1,040,71,816.13703,08
4x107 x 1,350,71,818.65601,83
4x167 x 1,700,71,820.27951,150
4x257 x 2,140,91,821.811300,727
4x357 x 2,520,91,824.115150,524
4x5019 x 1,781,01,927.520100,387
4x7019 x 2,141,12,031.728600,268
4x9519 x 2,521,12,135.438700,193
4x12037 x 2,031,22,339.248500,153
4x15037 x 2,251,42,443.859800,124
4x18537 x 2,521,62,648.774800,0991
4x24061 x 2,251,72,854.497350,0754
4x30061 x 2,521,83,059.9121200,0601



Contact us
Products
Projects